1 Answers
I have a pressurised mains water heating system. There is a small red tank above the central heating boiler. Attached to it there is a valve with a pressure meter connected (set at 3 bar but reading 2bar). The pressure meter appears to be connected to several pipes in a U configuration. One of these pipes is routed through to the outside of my house. It is this pipe which is constantly dripping water. Is this normal or is there a problem and if so what could it be?
Answers
Best Answer
No best answer has yet been selected by mcgubart. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.The exterior pipe will leak when the pressure has dropped. The system must be re-pressurised. There should be a car type valve on top of the red cylinder. This needs to be inflated with air. A tyre pump may be suitable. The pressure will drop over time. This is normal, but if it has suddenly happened, there may be a leak. Best to get a plumber.