Quizzes & Puzzles38 mins ago
High boiler pressure
4 Answers
Last year changed all plumbing in the flat, new boiler, pipes, rads etc. Since, the boiler pressure is above 3 both when on and off. When release water from rads the pressure falls but usually goes back above 3 over night. Checked mains valve - not leaking. Corgy guy looked at boiler, said its fine... Does anyone know what might be the cause and how to solve it?
thank you in advance
thank you in advance
Answers
Best Answer
No best answer has yet been selected by vladmeero. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.Sounds to me like your filling loop on your boiler is passing, can`t be anyhing else, providing its all piped up ok.If it only goes up when you use it , it could be your expansion vessel thats gone, but if it goes up on its own when there is no use from it, mains water is entering the system causing the pressure to rise. You will probably find the pressure relief pipe outside is dripping as well.
Does your boiler have an external or internal filling loop? Extrnal one will have a flexible silver hose conected from a 15mm pipe(cold water) to a 22mm pipe(return to boiler). If it has make sure the tap conected to the flexi pipe is turned off and slowly disconect it. If when you start to pull it away, water starts squirting out you know thats where your problem lies. You could always try turning your water off over night.(drop your pressure to about 1bar first). If it hasn`t risen then you know that mains water is entering the system.