Quizzes & Puzzles14 mins ago
CH/hot Water
6 Answers
Just recently the hot water coming from the taps is quite hot although we have set the programmer to CH only. What is the likely cause? There is a diverter valve in the system, could this be causing the problem? The manual lever on top of the diverter can be moved. Should it function automatically or can I set it to one of the 3 positions whatever they are?
Answers
Best Answer
No best answer has yet been selected by rov1200. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.It should function automatically but you can manually move it aswell. Ours broke and moving it manually didn't completely turn one or the other off (it was annoying having the heating on in summer when we just wanted hot water!) so we bought a new valve. It cost about �60 from a plumbing shop and didn't take long to fit and now works perfectly. I think plumbers charge around �200 to do it. The old one was all clogged up so we put some CH cleaner in the system and then inhibitor to keep the new one running smoothly.
if the system was installed correctly then the diverter valve motor gives priority to the hot water, so if it was broken you would get hot water but no heating.
it sounds as though it could be the actual body of the valve at fault and is passing water to both circuits.
i would be wary of fitting it yourself as you could end up very very wet.
it sounds as though it could be the actual body of the valve at fault and is passing water to both circuits.
i would be wary of fitting it yourself as you could end up very very wet.