boiler problem

Avatar Image
cherroo | 15:22 Mon 20th Nov 2006 | How it Works
3 Answers
Without checking first i think ive let too much water out of my radiators when bleeding them..duh i know...now the bolier lights up for about 20 secs and switches off again...help please...
Gravatar

Answers

1 to 3 of 3rss feed

Best Answer

No best answer has yet been selected by cherroo. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
There is every chance that you have lots of air in the system. The boiler lighting and shutting down is probably due to the boiler immediately overheating if the pump has de-primed.

You need to top the system back up - is it a combi-boiler ? If so it should have either and integral or external flling loop in order to top it up. Check with boiler instructions if you have them.
Good Luck.
switch your boiler off .underneath your boiler there should be a fill loop lever turn it till you hear water flowing check the pressure gauge on your boiler youll see the black needle moving turn the lever back to the normal position when your pressure gets to about 2 switch the boiler back on should be good
When you 'bleed' radiators, you are bleeding the air out of the system. This is replaced by water from the expansion tank or similar.
So assuming that the replacement feed is in order, you can't "let too much water out" when bleeding them!