when the electric switch goes on for the gas ch system to fire up it blows the house electrics......any ideas what the problem is; and is it easily fixed?
In the first instance, usual suspect is the pump (goes short circuit to earth). Try isolating it (by temporarily removing the connections to it) and see if the MCB / fuse still trips.
i'm guessing its an old style system rather than a modern combi type boiler, could be the pump but the last time i came across this problem it was actually the gas valve causing it.