flitty | 20:49 Thu 08th Nov 2012 | DIY
8 Answers
I have a closed system run off a combi boiler. The radiator downstairs is always cold even on high setting on the rad thermostat. I have bled it and the water comes out clean yet it remains freezing cold and the water coming out also is cold yet all other rads work. Any ideas ?
Gravatar

Answers

1 to 8 of 8rss feed

Best Answer

No best answer has yet been selected by flitty. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
Check the thermostat on/off control - it could be that the pin is stuck.
I agree with Tuvok. Stuck pin sounds right to me.
Question Author
sorry if i am being ignorant but where is the pin and how do i get at it
Does your thermostat lokk similar to this

http://www.google.co....HYDg&ved=0CKwBEPICMA0

If so, you take off the bit with the numbers and find the pin in there. Or get a friend to do it for you. Just pull the pin out and put it back in - you want movement in the pin.
Question Author
its a really old one with numbers on
Look at where it joins the radiator. Do you see where it clamps on - unscrew the screw holding the clamp tight. Take the numbered bit and clamp assembly off. Do you see the pin? Pull it out - probably need a pliers. Put it back in - then press it - does it feel like its moved in? Now put the numbered bit ack on, tighten it and finger crossed it will work when you turn it.
I had to do this each year in my work office!
Any luck with the pin Flitters?
It should spring up on its own after you've removed the head (knob with numbers on it).
If it's stuck down, tap it a few times with a mallet.