Quizzes & Puzzles11 mins ago
balanceing heating system,s
Please help
The best way to balance the red's in heating system
Many thanks
Answers
No best answer has yet been selected by packadarm. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.Look here, where this same question has been answered before. http://www.ebuild.co.uk/forums/messages/3322/6125.html p>
packadarm, First of all, ensure that the boiler is in heating mode.You need to adjust the " lockshield " valve on the side of each radiator. ( this is the one that you can't normally turn off because it has a smooth plastic cover over it ). Then, ensure that the normal valve is fully open. Give the lockshield valve cover a good sharp tug upwards ot remove .The lockshield valve is then adjusted up or down by using a suitable small spanner until a temperature difference of 11 degrees C is attained between the flow and return pipes. This needs to be done to every radiator ( unless one of the radiators is designed to be a by-pass , this one would stay fully open )
Hope this helps.
Related Questions
Sorry, we can't find any related questions. Try using the search bar at the top of the page to search for some keywords, or choose a topic and submit your own question.